The IF series of current sensors are rugged locomotive, industrial devices. These sensors accurately measure dc and ac currents and provide electrical isolation between the output of the sensor and the current carrying conductor. IF Series Data Sheet - This file is in PDF format, and is a section of the current sensor catalog. | Measuring Circuit | Units | IF-1000 | IF-2000 | IF-3000 | | Full scale (FS) dc or ac | +A | 1000 | 2000 | 3000 | | Fequency range | Hz | 1k | 1k | 1k | | Output | | | | | | Full scale output | V | 10.0 | 10.0 | 10.0 | | Sensitivity | mV/A | 10 | 5.0 | 3.3 | | Linearity (at +25°C) | % F.S. | 0.5 | 0.5 | 0.6 | | Maximum zero offset (at +25°C) | +mV | 50 | 50 | 50 | | Influence on Accuracy | | | | | | Maximum offset drift with temperature | +mV/oC | 2.0 | 2.0 | 2.0 | | Maximum sensitivity drift with temperature | +%/oC | 0.02 | 0.02 | 0.02 | | Withstand Capabilities | | | | | | Dielectric test | kV | 2.5 | 2.5 | 2.5 | | Output short or opern | | No Damage | No Damage | No Damage | | General Information | Units | IF-1000 | IF-2000 | IF-3000 | | Supply voltage | +V | 15 | 15 | 15 | | Operating temperature range | oC | -30 to +75 | -30 to +75 | -30 to +75 | | Storage temperature range | oC | -40 to +85 | -40 to +85 | -40 to +85 | | Aperture opening | inches (mm) | 1.67 (42.4) | 1.67 (42.4) | 1.67 (42.4) | | Weight | kgrams | 1.5 | 1.5 | 1.5 | Due to continuous process improvement, specifications are subject to change without notice. |